Abstract
This paper describes the performance of a 200-kV wideband reference voltage divider for calibration purposes. The divider is constructed to have a flat frequency response from DC up to c. 10 MHz. The main use of the divider is on-site calibration of AC, DC and impulse measuring systems. It can also be used for calibration of VLF, combined and composite voltage measuring systems.
| Original language | English |
|---|---|
| Title of host publication | 2024 Conference on Precision Electromagnetic Measurements, CPEM 2024 - Proceedings |
| Publisher | IEEE Institute of Electrical and Electronic Engineers |
| ISBN (Electronic) | 9798350361049 |
| DOIs | |
| Publication status | Published - 2024 |
| MoE publication type | A4 Article in a conference publication |
| Event | Joint 2024 NCSL International Annual Workshop and Symposium / Conference on Precision Electromagnetic Measurements, CPEM 2024 - Denver, United States Duration: 6 Jul 2024 → 12 Jul 2024 |
Conference
| Conference | Joint 2024 NCSL International Annual Workshop and Symposium / Conference on Precision Electromagnetic Measurements, CPEM 2024 |
|---|---|
| Country/Territory | United States |
| City | Denver |
| Period | 6/07/24 → 12/07/24 |
Keywords
- High-voltage divider
- high-voltage techniques
- measurement techniques
- measurement uncertainty
- metrology
- universal divider
- voltage measurement