TY - GEN
T1 - Design and Verification of a Calculable Composite Voltage Calibrator
AU - Havunen, Jussi
AU - Hällström, Jari
AU - Meisner, Johann
AU - Gerdinand, Frank
AU - Elg, Alf-Peter
PY - 2022/7/5
Y1 - 2022/7/5
N2 - Components used in the power grid need to be tested to verify they can withstand specified voltage stresses. Composite voltage test according to IEC 60060-1:2010 is a test method where impulse voltage is applied simultaneously with AC or DC voltage to the same terminal of the test object. To provide traceability to instruments used for composite voltage measurements, low-voltage calibrator based on combining existing calibrators was developed. The developed composite voltage calibrator can generate lightning and switching impulses together with DC and AC. The calibrator design is based on a series connection of a DC/AC calibrator and a calculable impulse voltage calibrator. Maximum impulse voltage peak is 330 V whereas the DC/AC voltage can be within 1000 V. Reference parameters for composite waveshape are calculated based on the applied voltage, charging voltage of the impulse calibrator, internal impedance of the impulse calibrator, and the input impedance of the device under calibration. The main uncertainty components of this composite voltage calibrator are the uncertainties related to the separate calibrators and the uncertainty of the load impedance needed for the parameter calculation.
AB - Components used in the power grid need to be tested to verify they can withstand specified voltage stresses. Composite voltage test according to IEC 60060-1:2010 is a test method where impulse voltage is applied simultaneously with AC or DC voltage to the same terminal of the test object. To provide traceability to instruments used for composite voltage measurements, low-voltage calibrator based on combining existing calibrators was developed. The developed composite voltage calibrator can generate lightning and switching impulses together with DC and AC. The calibrator design is based on a series connection of a DC/AC calibrator and a calculable impulse voltage calibrator. Maximum impulse voltage peak is 330 V whereas the DC/AC voltage can be within 1000 V. Reference parameters for composite waveshape are calculated based on the applied voltage, charging voltage of the impulse calibrator, internal impedance of the impulse calibrator, and the input impedance of the device under calibration. The main uncertainty components of this composite voltage calibrator are the uncertainties related to the separate calibrators and the uncertainty of the load impedance needed for the parameter calculation.
U2 - 10.5324/nordis.v27i1.4491
DO - 10.5324/nordis.v27i1.4491
M3 - Conference article in proceedings
T3 - Proceedings of the Nordic Insulation Symposium
BT - Proceedings of the 27th Nordic Insulation Symposium
PB - Nordic Insulation Symposium
T2 - 27th Nordic Insulation Symposium
Y2 - 13 June 2022 through 15 June 2022