Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay

Seppo Hänninen, Matti Lehtonen

    Research output: Book/ReportReport

    5 Citations (Scopus)

    Abstract

    This report describes three novel methods for earth fault location in unearthed, compensated and low-resistance grounded networks. The 20 kV medium voltage distribution networks are either unearthed or compensated in Finland. The last mentioned algorithm is therefore primarily intended for the export industry of the Finnish relay manufacturers. The developed algorithms are based on the use of fundamental frequency signals, and they need only one measurement unit per primary transformer at the substation. This is due to the fact that the fault current can be determined from the negative sequence component of the measured signal in the supply bay. The scope is restricted to radially operated systems. The earth fault distance location is based on the line impedance calculation in these algorithms. For unearthed and resistance grounded networks, measurements at three discrete times are needed for fault location purposes; pre-fault, fault and post-fault measurements. In the compensated network though, only two measurements, taken during the earth fault, are needed. The soundness of the algorithms was tested using simulated data. According to the results, the performance of the methods is good enough for practical use, and most likely the accuracy is comparable to the transient based methods. The algorithms were tested when the faulty feeder was both loaded and unloaded, with 10 - 30 W fault resistances. The error in distance computation was about 1- 2 km, depending on the loading and the fault resistance value.
    Original languageEnglish
    Place of PublicationEspoo
    PublisherVTT Technical Research Centre of Finland
    Number of pages43
    ISBN (Electronic)951-38-6066-3
    ISBN (Print)951-38-6065-5
    Publication statusPublished - 2002
    MoE publication typeNot Eligible

    Publication series

    SeriesVTT Tiedotteita - Research Notes
    Number2153
    ISSN1235-0605

    Fingerprint

    industry
    method
    distribution
    need
    calculation

    Keywords

    • power systems
    • power distribution networks
    • electrical faults
    • earth fault
    • positioning
    • fault resistance
    • distance
    • calculation
    • algorithms
    • signal processing

    Cite this

    Hänninen, S., & Lehtonen, M. (2002). Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay. Espoo: VTT Technical Research Centre of Finland. VTT Tiedotteita - Research Notes, No. 2153
    Hänninen, Seppo ; Lehtonen, Matti. / Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay. Espoo : VTT Technical Research Centre of Finland, 2002. 43 p. (VTT Tiedotteita - Research Notes; No. 2153).
    @book{80f042412c4e43e7b569a03b254d0bfa,
    title = "Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay",
    abstract = "This report describes three novel methods for earth fault location in unearthed, compensated and low-resistance grounded networks. The 20 kV medium voltage distribution networks are either unearthed or compensated in Finland. The last mentioned algorithm is therefore primarily intended for the export industry of the Finnish relay manufacturers. The developed algorithms are based on the use of fundamental frequency signals, and they need only one measurement unit per primary transformer at the substation. This is due to the fact that the fault current can be determined from the negative sequence component of the measured signal in the supply bay. The scope is restricted to radially operated systems. The earth fault distance location is based on the line impedance calculation in these algorithms. For unearthed and resistance grounded networks, measurements at three discrete times are needed for fault location purposes; pre-fault, fault and post-fault measurements. In the compensated network though, only two measurements, taken during the earth fault, are needed. The soundness of the algorithms was tested using simulated data. According to the results, the performance of the methods is good enough for practical use, and most likely the accuracy is comparable to the transient based methods. The algorithms were tested when the faulty feeder was both loaded and unloaded, with 10 - 30 W fault resistances. The error in distance computation was about 1- 2 km, depending on the loading and the fault resistance value.",
    keywords = "power systems, power distribution networks, electrical faults, earth fault, positioning, fault resistance, distance, calculation, algorithms, signal processing",
    author = "Seppo H{\"a}nninen and Matti Lehtonen",
    year = "2002",
    language = "English",
    isbn = "951-38-6065-5",
    series = "VTT Tiedotteita - Research Notes",
    publisher = "VTT Technical Research Centre of Finland",
    number = "2153",
    address = "Finland",

    }

    Hänninen, S & Lehtonen, M 2002, Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay. VTT Tiedotteita - Research Notes, no. 2153, VTT Technical Research Centre of Finland, Espoo.

    Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay. / Hänninen, Seppo; Lehtonen, Matti.

    Espoo : VTT Technical Research Centre of Finland, 2002. 43 p. (VTT Tiedotteita - Research Notes; No. 2153).

    Research output: Book/ReportReport

    TY - BOOK

    T1 - Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay

    AU - Hänninen, Seppo

    AU - Lehtonen, Matti

    PY - 2002

    Y1 - 2002

    N2 - This report describes three novel methods for earth fault location in unearthed, compensated and low-resistance grounded networks. The 20 kV medium voltage distribution networks are either unearthed or compensated in Finland. The last mentioned algorithm is therefore primarily intended for the export industry of the Finnish relay manufacturers. The developed algorithms are based on the use of fundamental frequency signals, and they need only one measurement unit per primary transformer at the substation. This is due to the fact that the fault current can be determined from the negative sequence component of the measured signal in the supply bay. The scope is restricted to radially operated systems. The earth fault distance location is based on the line impedance calculation in these algorithms. For unearthed and resistance grounded networks, measurements at three discrete times are needed for fault location purposes; pre-fault, fault and post-fault measurements. In the compensated network though, only two measurements, taken during the earth fault, are needed. The soundness of the algorithms was tested using simulated data. According to the results, the performance of the methods is good enough for practical use, and most likely the accuracy is comparable to the transient based methods. The algorithms were tested when the faulty feeder was both loaded and unloaded, with 10 - 30 W fault resistances. The error in distance computation was about 1- 2 km, depending on the loading and the fault resistance value.

    AB - This report describes three novel methods for earth fault location in unearthed, compensated and low-resistance grounded networks. The 20 kV medium voltage distribution networks are either unearthed or compensated in Finland. The last mentioned algorithm is therefore primarily intended for the export industry of the Finnish relay manufacturers. The developed algorithms are based on the use of fundamental frequency signals, and they need only one measurement unit per primary transformer at the substation. This is due to the fact that the fault current can be determined from the negative sequence component of the measured signal in the supply bay. The scope is restricted to radially operated systems. The earth fault distance location is based on the line impedance calculation in these algorithms. For unearthed and resistance grounded networks, measurements at three discrete times are needed for fault location purposes; pre-fault, fault and post-fault measurements. In the compensated network though, only two measurements, taken during the earth fault, are needed. The soundness of the algorithms was tested using simulated data. According to the results, the performance of the methods is good enough for practical use, and most likely the accuracy is comparable to the transient based methods. The algorithms were tested when the faulty feeder was both loaded and unloaded, with 10 - 30 W fault resistances. The error in distance computation was about 1- 2 km, depending on the loading and the fault resistance value.

    KW - power systems

    KW - power distribution networks

    KW - electrical faults

    KW - earth fault

    KW - positioning

    KW - fault resistance

    KW - distance

    KW - calculation

    KW - algorithms

    KW - signal processing

    M3 - Report

    SN - 951-38-6065-5

    T3 - VTT Tiedotteita - Research Notes

    BT - Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay

    PB - VTT Technical Research Centre of Finland

    CY - Espoo

    ER -

    Hänninen S, Lehtonen M. Earth fault distance computation with fundamental frequency signals based on measurements in substation supply bay. Espoo: VTT Technical Research Centre of Finland, 2002. 43 p. (VTT Tiedotteita - Research Notes; No. 2153).