EURAMET #1172: Bilateral three-phase AC power and energy comparison at power frequency

    Research output: Book/ReportReport

    Abstract

    The report summarizes the results of EURAMET project # 1172 on a bilateral comparison of power and energy measurement capabilities in MIKES, Finland and SP, Sweden in 2010-2011. A portable three phase reference energy meter was calibrated by the two institutes. Both active and reactive power as well as active and reactive energy measurements were compared. The expanded comparison uncertainty (k=2) ranged from 0.015 % for active power up to 0.06 % for some reactive power measurements. All measured values agreed within the expanded comparison uncertainties.
    Original languageEnglish
    Place of PublicationEspoo
    PublisherCentre of Metrology and Accreditation (MIKES)
    Number of pages18
    ISBN (Print)978-952-5610-98-7
    Publication statusPublished - 2012
    MoE publication typeD4 Published development or research report or study

    Publication series

    SeriesMIKES Publication
    NumberJ2/2012
    ISSN1235-5704

    Keywords

    • interlaboratory comparison
    • energy measurement

    Fingerprint

    Dive into the research topics of 'EURAMET #1172: Bilateral three-phase AC power and energy comparison at power frequency'. Together they form a unique fingerprint.

    Cite this