Abstract
Extinguishing experiments on post-flashover room fires, using various kinds of portable extinguihers or water jets, are reported. Typically 2–3 kg of AB-type (general purpose) powders were required to put out test fires of almost 5 MW heat release rate. With water the minimum flow for extinction was 17 l/min or 7.5 g/m2 s. When halon or B-type powder was used the fire re-ignited.
Original language | English |
---|---|
Pages (from-to) | 201-209 |
Journal | Fire Safety Journal |
Volume | 11 |
Issue number | 3 |
DOIs | |
Publication status | Published - 1986 |
MoE publication type | A1 Journal article-refereed |