title = "Extinguishment of liquid fires with sprinklers and water sprays: Analysis of the test results",
abstract = "A series of extinguishing tests was carded out on ten liquids with a flash point in the range of -6 °C to 234 °C applying seven different sprinklers or nozzles. Pool size was varied within the range 0.4 m2 - 12 m2, and the nozzle height within the range 3 m-8 m. In this publication the results of the tests are analysed. Free bum data are considered in detail. Observations and effects of pool size, nozzle type, flash point, application rate, preburn time and nozzle height are discussed. Recommendations are made on the required application rates. A method of testing the applicability of sprinklers or nozzles against liquid pool or spill fires is proposed.",
keywords = "extinguishing, fire extinguishers, sprinklers, fire protection, nozzles, sprayers, liquids, analyzing, methods, proposals, flash point, tests",
author = "Matti Kokkala",
year = "1990",
language = "English",
isbn = "951-38-3718-1",
series = "Valtion teknillinen tutkimuskeskus. Tutkimuksia - Research Reports",
publisher = "VTT Technical Research Centre of Finland",
number = "696",