Skip to main navigation Skip to search Skip to main content

Fire safety of alcoholic beverages in retail stores

  • Tuula Hakkarainen*
  • , Timo Korhonen
  • , Jukka Vaari
  • *Corresponding author for this work

    Research output: Contribution to journal › Article › Scientific › peer-review

    Abstract

    A fire test series to study pool fires of ethanol-water mixtures in the small, intermediate and large scale has been performed. Additionally, demonstration tests of piles of PET plastic 0.5-L liquor bottles (39 vol%) in retail store arrays were carried out to illustrate their burning behaviour. On the basis of the test results, the burning of pool fires of different alcoholic beverages and the fire load due to alcohol can be evaluated for the purpose of performance-based fire safety design. The fire tests of retail store arrays showed that these fires grow slowly, and their heat release rate maxima are relatively low taking into account the mass of the fire load. The estimated heat release rate maxima of four-layer retail store arrays were ca. 1.5 MW and their growth times were over 600 seconds. Design fires generally used for the fire safety design of shopping centres are typically much more severe than the fire test results of retail store arrays of alcoholic beverages in this study.
    Original languageEnglish
    Pages (from-to)1044-1050
    Number of pages7
    JournalFire and Materials
    Volume45
    Issue number8
    Early online date26 Feb 2021
    DOIs
    Publication statusPublished - Dec 2021
    MoE publication typeA1 Journal article-refereed

    Keywords

    • alcohol fires
    • design fires
    • fire testing
    • heat release
    • performance-based fire safety design
    • pool fires

    Fingerprint

    Dive into the research topics of 'Fire safety of alcoholic beverages in retail stores'. Together they form a unique fingerprint.