Abstract
The main objective of the project was to show that
lowering the cost of district heating (DH) is possible by
using demand side management (DSM). The practical
installation of DH DSM in a building is not expensive.
Peak cut of 25-30 % is going to be achieved with
exploiting the thermal mass of the building and by
properly controlling the heating system. Indirect savings
will also be evaluated. Hot tap water was not included in
DSM.
There were three case study buildings, two in Jyväskylä
Finland and one in Mannheim Germany, where the DSM
demonstrations were carried out. A calculation tool for
test buildings has been developed for quick evaluation of
proper DSM possibilities. The characteristic model of
buildings is described using thermal capacity-resistance
description.
The research made in two Finnish case study buildings
shows that the maximum heat load of a massive building
(body of concrete) can be during 2-3 hours reduced as
much as 20-25 % on the average because of the thermal
capacity of radiator heating network. When the
circulation water reaches the set DSM temperature level
the heating load starts to increase up to the load level
defined by any current DSM temperature setting. The loads
of intake air heating are large but the thermal capacity
of ventilation intake air heating is small compared to
large room heating radiator systems. As the temperature
change of ventilation can be felt immediately the
DSM-control measures of ventilation must be very small
and sensitive while the building is in a normal use. The
only way to keep the heat demand of intake air heating
low during the DH DSM operations is to slightly reduce
the air flow temperatures by 1-2 °C.
Peak cut of 20 % in Jyväskylä means about 160 buildings
of the volume 20 000 m3. Based on simulations how to use
energy production capacity in DSM, the total saving is
evaluated 13 000 /a in the Jyväskylä case. Thus a DSM
investment of 845 per consumer (5 %, 15 a) is aloud. If
we assume to save an investment of 20 MW HOB (1,8 milj.
EUR) because of DSM and we divide it to 20 years with 5 %
interest, the additional saving will be 144 000 /a and
in addition maintenance and other fixed costs. It means
an investment of about 10 000 per consumer in the
Jyväskylä case.
In the German Tower Block case in Mannheim the daily heat
demand peak could be reduced by 4.1 %. This increases the
efficiency of heat production at the power plant on the
average by 3 %. This increased efficiency has been
reached during peak demand time, which means during 1-2
hours per day. By simply closing the valve larger
reductions would be possible during very short time
periods. This is no option because the subsequent peak
when reopening the valve would actually increase the
daily maximum. It is not feasible to shift peaks in this
way to times of low demand in the district heating
network because the relevant time span (around three
hours) is far too long.
The building is equipped with an air heating system and a
computer based control system which tends to start the
air conditioning system earlier when outdoor temperature
is lower. It does so in order to insure the desired
indoor temperature of 21.5 °C at 6:30 a. m. By doing so
the computer system automatically flattens the daily heat
demand when outdoor temperature is low. As a consequence
it was not possible to achieve further peak reductions
with DSM measures when the outdoor temperature is very
low (<0 °C). The time constant of the air heated building
is shorter than of buildings with radiator heating.
Two kinds of tariff structure is recommended. A fixed
agreement, where supplier has the right to cut daily peak
load of the consumer by remote control in agreed limits
up to 25 % of connected capacity and for a maximum 3 hour
per day in one or two periods. The consumer can have some
discount in fixed annual payments. The post heating
period should be 1.5-2 hours longer than cut period and
the thermal effect should be returned linearly to avoid
the remarkable post heating peak in the buildings. In
other case the consumer can decide how he cuts his peak
load. Hourly peak load a day will be measured and based
on the maximum annual or monthly peak load he must pay a
fix thermal power capacity payment a year.
| Original language | English |
|---|---|
| Place of Publication | Espoo |
| Publisher | VTT Technical Research Centre of Finland |
| Number of pages | 104 |
| ISBN (Electronic) | 951-38-6472-3 |
| Publication status | Published - 2004 |
| MoE publication type | Not Eligible |
Publication series
| Series | VTT Tiedotteita - Meddelanden - Research Notes |
|---|---|
| Number | 2247 |
| ISSN | 1235-0605 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- demand side management
- DSM
- district heating systems
- buildings
- testing
- test buildings
- measurement
- control devices
- data collection
- data analysis
Fingerprint
Dive into the research topics of 'Kysynnän hallinta kaukolämpöjärjestelmissä'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver