Abstract
In this paper, overvoltage transients are investigated and mitigated when a three-phase short-circuit occurs in cable lateral connected with medium voltage (MV) overhead line and fuse is operated. The transients are studied using EMTP-ATP simulation environment and the need of metal oxide varistors (MOVs) is investigated. The cable laterals consist of sub-laterals and their effect on reducing transients is also investigated. The surge arresters are installed at the junction of overhead line and cable and at far end of the cable near short-circuit point. The different mitigation methods are tested and optimal protection scheme to reduce overvoltages is proposed on the basis of surge arresters locations and sub-lateral connections.
Original language | English |
---|---|
Pages (from-to) | 107-110 |
Journal | Elektronika ir Elektrotechnika |
Volume | 107 |
Issue number | 1 |
Publication status | Published - 2011 |
MoE publication type | A1 Journal article-refereed |