Abstract
This paper describes an outdoor calibration of an instrument current transformer connected to 400 kV transmission line. The method of generation of the high current and the accuracy of calibration are discussed. The reference current measuring system consists of a current shunt, a Rogowski coil, two digitizing voltmeters and a computer to control voltmeters. The Rogowski coil is calibrated on-site with the current shunt. The output voltage of the Rogowski coil is not integrated, but it is scaled according to the on-site calibration result. Estimated uncertainties for ratio and phase displacement are less than 0,01 % and 100 μrad, respectively.
Original language | English |
---|---|
Title of host publication | 2008 Conference on Precision Electromagnetic Measurements Digest, CPEM 2008 |
Publisher | IEEE Institute of Electrical and Electronic Engineers |
Pages | 468-469 |
Number of pages | 2 |
ISBN (Electronic) | 978-1-4244-2400-9 |
ISBN (Print) | 978-1-4244-2399-6 |
DOIs | |
Publication status | Published - 23 Sept 2008 |
MoE publication type | A4 Article in a conference publication |