Abstract
This paper describes a reference current-measuring system for the onsite calibration of high-voltage current transformers. The reference current-measuring system consists of a Rogowski coil, a current shunt, two digitizing voltmeters, and a computer to control the voltmeters. The method of generation of the high current and the uncertainty of the calibration are discussed. The results of a calibration performed onsite on a 400-kV substation are presented. Uncertainties of 300 muA/A for ratio and 1 angular minute for phase displacement were achieved with this method onsite.
| Original language | English |
|---|---|
| Pages (from-to) | 1054-1058 |
| Journal | IEEE Transactions on Instrumentation and Measurement |
| Volume | 58 |
| Issue number | 4 |
| DOIs | |
| Publication status | Published - 2009 |
| MoE publication type | A1 Journal article-refereed |
Keywords
- High current
- Rogowski coil
- high voltage
- instrument current transformer (CT)
- onsite calibration