Abstract
The subject of this thesis is the single phase earth
fault in medium voltage distribution networks that are
high impedance grounded. Networks are normally radially
operated but partially meshed. First, the basic
properties of high impedance grounded networks are
discussed. Following this, the characteristics of earth
faults in distribution networks are determined based on
real case recordings. Exploiting these characteristics,
new applications for earth fault indication and location
are then developed.
The characteristics discussed are the clearing of earth
faults, arc extinction, arcing faults, fault resistances
and transients. Arcing faults made up at least half of
all the disturbances, and they were especially
predominant in the unearthed network. In the case of
arcing faults, typical fault durations are outlined, and
the overvoltages measured in different systems are
analysed. In the unearthed systems, the maximum currents
that allowed for autoextinction were small. Transients
appeared in nearly all fault occurrences that caused the
action of the circuit breaker. Fault resistances fell
into two major categories, one where the fault
resistances were below a few hundred ohms and the other
where they were of the order of thousands of ohms.
Some faults can evolve gradually, for example faults
caused by broken pin insulators, snow burden, downed
conductor or tree contact. Using a novel application
based on the neutral voltage and residual current
analysis with the probabilistic method, it is possible to
detect and locate resistive earth faults up to a
resistance of 220 kW.
The main results were also to develop new applications of
the transient based differential equation, wavelet and
neural network methods for fault distance estimation. The
performance of the artificial neural network methods was
comparable to that of the conventional algorithms. It was
also shown that the neural network, trained by the
harmonic components of the neutral voltage transients, is
applicable for earth fault distance computation. The
benefit of this method is that only one measurement per
primary transformer is needed. Regarding only the earth
faults with very low fault resistance, the mean error in
absolute terms was about 1.0 km for neural network
methods and about 2.0 km for the conventional algorithms
in staged field tests. The restriction of neural network
methods is the huge training process needed because so
many different parameters affect the amplitude and
frequency of the transient signal. For practical use the
conventional methods based on the faulty line impedance
calculation proved to be more promising.
Original language | English |
---|---|
Qualification | Doctor Degree |
Awarding Institution |
|
Supervisors/Advisors |
|
Award date | 17 Dec 2001 |
Place of Publication | Espoo |
Publisher | |
Print ISBNs | 951-38-5960-6 |
Electronic ISBNs | 951-38-5961-4 |
Publication status | Published - 2001 |
MoE publication type | G5 Doctoral dissertation (article) |
Keywords
- power distribution
- distribution networks
- earth faults
- detection
- positioning
- fault resistance
- arching
- neutral voltage
- residual current
- transients